Customization: | Available |
---|---|
Usage: | Emergency Light |
Emergency Time: | 3-4h |
Still deciding? Get samples of US$ 18/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Relevant Standard
EN 60598-1 |
EN 61000-3-2 |
IEC 60598-1 |
IEC61000-3-2 |
EN 60598-2-22 |
EN 61000-3-3 |
IEC 60598-2-22 |
IEC 61000-3-3 |
EN 61347-1 |
EN 62471 |
IEC 61347-1 |
IEC 62471 |
EN 61347-2-13 |
EN 62493 |
IEC 61347-2-13 |
IEC 62493 |
EN 61347-2-7 |
EN 55015 |
IEC 61347-2-7 |
IEC 55015 |
EN 62778 |
EN62031 |
IEC 62778 |
IEC62031 |
Product Parameter
Model No.: |
LEK02-3NC |
Battery: |
Ni-Cd, 3.6V 2000mAh |
LED Chips: |
CREE XT-E |
Luminous Flux: |
150lm |
Power Consumption: |
3W |
Input Voltage: |
AC220-240V~50/60Hz |
Charge time: |
24Hours |
Emergency duration: |
3Hours |
ta: |
0~35ºC |
Max. Case Temp.: |
70ºC |
Protection Class: |
II |
IP Rating: |
IP20 |
Operation: |
Non-maintained |
Function: |
AUTO test |
Dimension
Installation Diagram
Wire preparation:
0.5~1.5mm²
AUTO Test
∷ Commissioning test-
Connection of the mains supply will initiate commissioning where the battery will remain on charge for an uninterrupted 24 hours; An interruption of the mains supply will reset the counter to zero.
After 24hours, the luminaire will be put into a duration test for the rated period, immediately followed by another 24hr charge period.
∷ Function test-
A 5 second functional test is carried out at 1 week interval.
∷ Duration test-
A full rated duration test is carried out at 13 weeks intervals.
System status is indicated by a bi-color LED.
LED indication |
Status |
Commentary |
Permanent green |
Everything works correctly |
|
One flashed 4 seconds pause |
Battery failure |
Battery is not connected |
Two flashed 4 seconds pause |
Battery failure |
Battery short or low battery Voltage |
Three flashed 4 seconds pause |
Load failure |
LED failure |
Green and Red off |
DC mode |
Battery operation (Emergency mode) |
Special Notes
∷ This product should be installed by a registered electrician in accordance with local standards and electrical regulations;
∷ Take care to ensure the mains supply is isolated before installation;
∷ The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced;
∷ The whole luminaire should be replaced when they no longer meet their rated duration of operation after the corresponding recharge period.